Delivery of five (5) variable Shunt Reactor for outdoor installation at the following substations Gørløse, Hovegård and Malling Rated voltage Ur: 400 kV Power rating: 70-140 Mvar Regulation Range: 50 % or above Type of regulation: onload (OLTC) Cooling: ONAN Maximum sound power level: 84 dB(A), preferably lower, (at max. operating voltage 420 kV) Corrosion Protection: C5VH or above Max. operating voltage Umax: 420 kV Frequency: 50 Hz Magnetic characteristic: The core must be linear up to 1.5 times rated voltage.
Delivery of five (5) variable Shunt Reactor for outdoor installation at the following substations Gørløse, Hovegård and Malling Rated voltage Ur: 400 kV Power rating: 70-140 Mvar Regulation Range: 50 % or above Type of regulation: onload (OLTC) Cooling: ONAN Maximum sound power level: 84 dB(A), preferably lower, (at max. operating voltage 420 kV) Corrosion Protection: C5VH or above Max. operating voltage Umax: 420 kV Frequency: 50 Hz Magnetic characteristic: The core must be linear up to 1.5 times rated voltage.