New office building for young companies on the old slaughterhouse in Karlsruhe, the building has no basement, has 6 floors and a gross floor area of 3,980 m
Services for heating and cooling systems are advertised.
- 1 piece of reversible sole-water heat pump for indoor installation approx. 130 kW heat output and approx. 110 kW cooling output,
- Black steel threaded pipe with fittings for heating water DN 15 - DN 32: approx. 110 m Steel threaded pipe black with fittings for heating water DN 40 - DN 80: approx. 150 m,
- galvanized steel pipe with fittings for heating water DN 15 - DN 25: approx. 1 100 m,
- galvanized steel pipe with fittings for heating water DN 32 - DN 50: approx. 350 m,
- Black steel threaded pipe with fittings for air conditioning cold water DN 15 - DN 32: approx. 175 m,
- Black steel threaded pipe with fittings for cold air water DN 40 - DN 100: approx. 265 m,
- 3-row convector radiator in the color anthracite, in size T / H / L = 194/140/1 500 mm,
- 42 pieces 3-row convector radiators in the color anthracite, in the size T / H / L = 194/210/1 500 mm,
- 26 pieces of 3-row convector radiators in the color anthracite, in size T / H / L = 194/280/1 700 mm,
- 22 white flat radiators, in size H / L = 905 / 405-905 mm,
- 8 white heating panels, in size H / L = 1800-2000 / 700-1050,
- 6 ceiling fan coil units for cooling with a cooling capacity of up to 4.3 kW,
- 7 pieces of mineral wool insulation for heating pipes DN 15 - DN 80: approx. 1 700 m,
- Cold insulation made of flexible elastomer foam for cooling pipes DN 15 - DN 100: approx. 440 m.