Design, manufacture, installation and testing of a CE-marked 150 MJ/s horizontal U-tube type district heater on a 1:1 replacement basis.
Design, manufacture, installation and testing of a CE-marked 150 MJ/s horizontal U-tube type district heater on a 1:1 replacement basis. ‘1:1 replacement’ means that the new heater must comply with the physical and thermodynamic restrictions given by the original design and physical location of the heater:
Design pressures: 4/-1 bar (steam side) and 29 bar (water side).
Design temperatures: 100°C (steam side) and 100°C (water side).