Installation of emergency call and operations control centre in existing building. Cloakrooms and parts of the technical rooms on the upper floor, office and social rooms on the attic floor; Technical centres partly on roof. Operating hours 7 x 24 x 365; Availability requirement 99.999%.
2 emergency generators incl. fuel supply system: rated power 300kVA, diesel engine, exhaust pipe, silencer, particulate filter, electric cabinet with emergency power control, tank system
2 pcs. main distributions, 4 pcs. sub-distributions normal network, 4 pcs. sub-distributions UPS network, 2 pcs. sub-distributions operations center UPS network
Connections, earthing, protection equipotential bonding, pipe systems, 570m cable trays 200mm-500mm, main and risers, light installations, power installations, HVAC installations
Fiber optic and UKV supply line/distributor, 2 hot aisle containments with 12 units each UKV distributor, UCT, intrusion / hold-up alarm, access control, video surveillance, multimedia and fire alarm installation
Control system & backup server, workstations, software: 688 hardware and 3,100 communicative data points, 1500 Modbus/RTU, 75 plant/room & overview images, 5 tables, 50 trend compilations