UW TREYSA - ERNEUREUNG 20 kV SWITCHGEAR
Supply, installation and commissioning support of a 19-field 24 kV SF6 gas insulated switchgear;
Double busbar, with vacuum switches, max. rated voltage 24 kV, with a rated current of 2000 A and nominal short-term current of 25 kA (3s).
Installation and commissioning support of the digital protection control units and the secondary technical connection of the 110 kV transformers and earth fault compensation systems.
Delivery, installation and commissioning support to secondary equipment to be supplied or provided, such as control cabinets, components of the open-air system, 230/400 V AC or 110 V DC supply as well as the building installation such as lighting, heating and sockets, etc. Partial expansion of new 24 kV cable trays and cable duct/pipe system for secondary cabling Buildings up to 110 kV open-air system.
Supply, installation and commissioning support of a 19-field 24 kV SF6 gas insulated switchgear; Double busbar, with vacuum switches, max. rated voltage 24 kV, with a rated current of 2000 A and nominal short-term current of 25 kA (3s). Attention: Modification of the technical specification in area 3.1 Busbar connections.
Installation and commissioning support of the digital protection control units and the secondary technical connection of the 110 kV transformers and earth fault compensation systems.
Delivery, installation and commissioning support to secondary equipment to be supplied or provided, such as control cabinets, components of the open-air system, 230/400 V AC or 110 V DC supply as well as the building installation (such as lighting, heating and sockets, etc.).
Partial expansion of new 24 kV cable trays and cable duct/pipe system for secondary cabling building up to 110 kV open-air system.
Delivery and installation of a 5-field e-coil switchgear including the primary and secondary cabling.
Cable routing, assembly and connection of 20 kV cables provided on site.
Documentation of the complete primary and secondary technology.
All project management and documents must be prepared in German.
All versions according to relevant IEC, EN or DIN standards, as well as applicable VDE regulations and VDEW recommendations according to the latest state of the art.