The building to be constructed is planned for use as an administrative building. In the resulting cubature, office use, including associated social, storage and technical rooms, as well as associated traffic areas are planned on 5 full and one staggered floors. In addition to the own space on the four lower levels, reserve space and space for third-party letting with administrative and commercial use are provided for the 4th floor and the second floor.
- Central battery system with 28 circuits for emergency lighting,
- Low voltage main distribution:
—— EVU feeder field with converter counter,
—— outgoing panel with 10 safety elements,
- Meter cabinet combination with 6 meter spaces,
- General distributor for the general consumers of the building:
—— 1 x main switch as switch disconnector,
—— 1 x Dehn surge protector type 2, 3-pin. .
—— 1 x 3-pole group FI switch, per group with subsequent 6 x miniature circuit breakers B16A, ´
—— 5 x miniature circuit breakers B16A,
—— 10 x miniature circuit breakers B10A,
—— 1 x 3-pole group FI switch, per group with subsequent,
—— 2 x FI-LS B10A,
—— 10 x FI-LS B16A, 2-pin. for individually protected circuits,
—— 2 x miniature circuit breakers C25A, 3-pin. .
—— 2 x circuit breakers C16A, 3-pin. .
—— 2 x circuit breakers C16A, 3-pin. .
—— 2 x miniature circuit breakers B6A, 1-pin. .
—— 1 x astro watch, 2-channel,
- 6 floor distributors as stand distributors:
—— 1 x main switch as switch disconnector
—— 1 x Dehn surge protector type 2, 3-pin,
—— 5 x 3-pole group FI switches, per group with subsequent ones
—— 6 x miniature circuit breakers B16A,
—— 2 x 3-pole group FI switches, per group with subsequent ones
—— 6 x miniature circuit breakers B10A and 12x auxiliary switches for DALI bus isolation
—— 1 x 3-pole group FI switch, per group with subsequent ones
—— 4 x miniature circuit breakers B10A and via motion detector control,
—— 23 x FI-LS B16A, 2-pin. for individually protected sockets,
—— 2 x miniature circuit breakers B20A, 3-pin. for fixed connections,
—— 10 x miniature circuit breakers B16A, 1-pin. for shutter actuators,
—— 10 x miniature circuit breakers B10A, 1-pin. for valve actuators,
—— 3 x miniature circuit breakers B6A, 1-pin. for permanent connections.
Power cables:
Different types of installation existing support systems, in pipe, cavity wall in wall slots
- 150 m halogen-free cable NHXMH-J 4 x 35 mm²,
- 230 m halogen-free cable NHXMH-J 4 x 25 mm²,
- 9 100 m ha approx. 9 100 m halogen-free cable NHXMH-J 3 x 2.5 mm²,
- NHXMH-J 3 x 2.5 mm² lead-free cable,
- 600 m halogen-free cable NHXMH-J 5 x 4 mm²,
- 3,000 m halogen-free cable NHXMH-J 5 x 2.5 mm²,
- 9 100 m halogen-free cable NHXMH-J 3 x 2.5 mm²,
- 2 350 m halogen-free cable NHXMH-J 3 x 1.5 mm²,
- 3,600 m halogen-free cable NHXMH-J 5 x 1.5 mm²,
- 5 m NYY-J 4 x 120 mm²,
- 5 m NYY-J 4 x 70 mm²,
- 40 m NYY-J 4 x 50 mm²,
- 400 m NYY-J 3 x 2.5 mm² buried
- 2 500 m E30 NHXH-J 3 x 2.5 mm².
Installation Equipment:
- 19 ceiling pillars,
- 11 pcs floor tanks,
- 20 m parapet canal,
- 400 pc sockets,
- 50 off switches,
- 90 presence detectors,
- 90 KNX buttons / controls.
Lighting systems:
- 200 St. recessed lights,
- 16 mirror lights,
- 30 pcs pendant lights,
- 120 St. downlights,
- 30 pcs staircase lights,
- 50 pictogram lights,
- 70 ready lights.
Equipment workplace:
Each AP receives 2 double sockets and 2 double data sockets
Office lighting is provided by recessed ceiling lights with daylight control (HCL)
External lightning protection system:
- 600 m catch and discharge lines,
- 25 pieces of interception rods,
- 400 m equipotential bonding line.