Delivery, installation and commissioning of an air-insulated 10 kV switchgear according to IEC 62271 with approx. 22 switch panels for a
Substation in Dusseldorf
Ready-to-use erection of a metal-encapsulated, air-insulated
10 kV switchgear with single busbar according to DIN EN
62271. The fields shall be equipped with vacuum circuit breakers.
The facility is expected to contain 16 outlet fields, two
Feed-in fields, two elevations and two measuring fields.
The exact number and specification will only be determined in the tender.
Technical specifications:
Single busbar
Feldteilung:
Einspeisefeld 1000 mm
Längskupplung 1000 mm
Hochführung 1000 mm
Abgangsfeld 650 mm
Messfeld 650 mm
SS rated current 2500 A
Einspeisefeld 2500 A
Abgangsfeld 630A /1250 A
Bemessungs-Kurzzeitstrom: 25 kA / 1s
The majority of the order is to be carried out with the company's own personnel. The planned factory acceptance test (FAT) of the switchgear must be able to take place in Europe.
The applicant must have his own assembly personnel, as well as testing and IBS personnel. Subcontractors must be notified to Netzgesellschaft Düsseldorf mbH (NGD) and approved by NGD. Subcontractors, for their part, may not subcontract on your part.
Side offers and proposed changes are not permitted.
Planned delivery period: approx. 3-4th quarter 2024