Building automation.
Connection to fiber optic network, automation bus BACnet / IP, programmable control, visualization on the control system, integration in alarm management, connection of the heat meter, water meter and electric meter via M-Bus (meter management), connection via MOD-Bus RTU => chiller
Connection via LON FTT10 => controller and operating devices
Activation via KNX => electrical engineering with lighting, blinds, window contacts, weather station etc.
Digital - manual control level in the control cabinet front, 19 "
=> A digital manual control level is required for motors (pumps, fans, etc.)
- Analogue - manual control level in the control cabinet front, 19 "
=> An analogue manual control level is required for control valves, FCs, and long-distance line pumps
- Digital - emergency operating level in the control cabinet front, 19 "
=> A digital manual control level is required for motors (pumps, fans, etc.)
- Analogue - emergency operating level in the control cabinet front, 19 "
=> An analogue manual control level is required for control valves, FCs, and long-distance line pumps
The following are to be delivered and integrated in this system:
=> 1 piece outside temperature sensor
=> 23 pieces of pipe sensor with brass immersion sleeve
=> 18 pipe sensors with stainless steel immersion sleeve
=> 1 piece safety pressure limiter pmin
=> 17 wall-mounted sensors
=> 3 immersion thermostats 0 to 70
=> 69 flush-mounted room sensors in the switch range with temperature sensor
=> 2 flush-mounted room sensors in the switch range with:
- temperature sensor
- Setpoint adjuster + -3K
- 2xLED
- with special printing
=> 6 pieces combination sensor temp. Humidity
=> 2 pieces of dew point monitors
=> 3 pieces of CO2 sensors, room version
=> 12 pieces of temperature sensors as cable sensors
=> 3 duct smoke detectors with VDS and DiBT approval
=> 2 pieces of frost protection thermostat
=> 4 pieces of differential pressure monitors for air
=> 14 air duct sensors
=> 5 pieces of damper actuators
=> 4 differential pressure transmitters for gaseous media
=> 5 small zone valves
=> 120 valve actuators VA 2002
=> 12 pieces three-way valve heating and cooling
=> 8-way heating and cooling valve
2672 data points connected to the ISPs
ISP01:
- Analog inputs: 146 pieces;
- Digital inputs: 338 pieces;
- Analog outputs: 44 pieces;
- Digital outputs: 150 pieces;
- Communicative M-Bus: 10 pieces;
- Communicative LON: 90 pieces;
- Communicative MOD-Bus: 76 pieces;
- Communicative KNX bus: 600 pieces.
ISP02:
- Analog inputs: 208 pieces;
- Digital inputs: 202 pieces;
- Analog outputs: 173 pieces;
- Digital outputs: 55 pieces;
- Communicative MOD-Bus: 20 pieces;
- Communicative KNX bus: 560 pieces.