MSR new building
MSR new building
1. ISP01 ventilation: approx. 380 data points, 5 control cabinet panels on the 2.UG and 5th floor, manual operation
- 5 supply air + exhaust air units, 1x adiabatic exhaust air cooling, 6x steam humidifier
- KV system heat recovery: integrated control, manual control level, BACnet connection
- Approx. 60 volume flow controllers, approx. 280 BSK (ASi-Bus system) BACnet connection, 12 JAL flaps
2. ISP02 heating: approx. 100 data points, 2 control cabinet panels in the 2.UG, manual control level
- Heating manifold with 7 outlets: 1x pump control valve per outlet, 2-3 sensors, switching H/K
- Fresh water station (BACnet connection); 16 BKE Med. gases via Modbus
3. ISP03 refrigeration: approx. 100 data points, 2 control cabinet panels in the 2.UG, manual control level
- Refrigeration distributor with 5 outlets: 1x pump control valve per outlet, 2-3 sensors, switching H/K
- Connection ELA, nurse call and 4 elevators
4. ISP04-06 MSR-RA: approx. 1700 data points, 4 control cabinet panels on the 1st-2nd-4th floor, approx. 10 controllers centrally in AV with approx. 105 room control units, approx. 130 sensors, approx. 145 valves (2/6-way), approx. 118 VSR, approx. 25 hygienic flush, approx. 22 ULK and room sensor, approx. 32 ELT distributors. Approx. 90 RTH 230V and zone valves conventional without I&C connection on the ground floor and 3rd floor.