A free-standing operating theatre building with basement (ground floor) + ground floor will be added to the existing clinic in Bad Windsheim as a new construction measure
in reinforced concrete construction. connected by means of two transition bridges in the ground floor.
Dimensions approx. 30m x 32m x h= 9.20m.
This new building + the two bridge structures will receive in the area of sanitary, heating, refrigeration and ventilation
new piping and pipe systems. These must be insulated accordingly.
Sanitary:
approx. 295 m insulation made of flexible polyethylene foam for sewage pipes DN50 - DN100
approx. 380 pcs insulation for fittings of sewage pipes DN50 - DN100
approx. 645 m Thermal insulation on cold water pipes made of diffusion-tight rock wool pipe shells DN12 - DN50
approx. 775 m thermal insulation on hot water and circulation pipes made of mineral wool shells DN12 - DN40
approx. 840 pcs insulation for fittings on water pipes
Heater:
approx. 1880 m Insulation of heating pipes as well as fittings and connecting parts made of carbon steel or black steel pipe DN12 - DN80
approx. 130 m sheet metal jacket on insulated heating pipes DN12 - DN80
approx. 90 pcs sheet metal sheathing on insulated heating fittings
Cold:
approx. 970 m synthetic rubber insulation, vapour diffusion-tight, including fittings and connectors, DN15 - DN150
approx. 140 pcs insulation with sheet metal jacket on fittings refrigeration technology DN15 - DN150
approx. 155 m sheet metal sheathing on insulated refrigeration pipes DN15-DN150
Ventilation:
approx. 370 m² thermal insulation of ventilation pipes and ducts made of mineral wool 30mm
approx. 600 m² Thermal insulation of fittings Ventilation technology made of mineral wool 30mm
approx. 610 m² cold insulation of ventilation pipes, fittings and ducts made of vapour-diffusion-tight synthetic rubber 19mm
approx. 150 m² sheet metal sheathing on insulated ventilation ducts and fittings