The scope of supply is one (1) heat pump unit equipped with one or 2 turbo compressor and with minimum of 9,5 MW cooling capacity.
The scope of supply is one (1) heat pump unit equipped with one or 2 turbo compressor and with minimum of 9,5 MW cooling capacity. Refrigerant R1234ze. The heat pump must be designed with the values described below: Cooling capacity (winter) 9,5 MW, District heating water out (max) 82
Condenser: Required heating capacity 11-15 MW. Tube material carbon steel.
Evaporator: Required cooling capacity minimum 9,5 MW. Tube material carbon steel. Maximum dimensions of the heat pump unit: 12 m x 6 m x 5 m (length x width x height). Supply voltage 6kV or 10 kV for the electric motor (will be determined in negotiations later). The control range of the heat pump shall be 30-100 %. Cooling COP minimum 3,5 and heating COP minimum 4 when district heating water out is 65
Availability of service: the supplier must be able to have an independent service at the heat pump station no later than within 48 hours after receiving a call from the client. This is essential from the standpoint of minimizing losses due to the production shutdown. The heat pump shall be designed in accordance with the EN standards and pressure equipment directive requirements. The heat pump unit in the scope of this procurement is one technical entity which cannot be divided into lots.