Exhibition and presentation of archaeological finds to the public; archaeological workshops for processing, securing and archiving archaeological finds, which are also open to the public as a show workshop; Conducting seminars and events.
Electrical installation in accordance with the applicable standards and regulations including low-voltage switchgear, emergency lighting control centers, laying systems, installation devices with KNX system, lighting, lightning protection system, potential equalization:
- Central emergency lighting system 70 Ah, individual light monitoring;
- Low-voltage main distribution with busbar 630 A, several fields;
- Meter cabinet with 4 meter spaces;
- approx. 40,000 m halogen-free cables and wires for low-voltage installations, telecommunications systems, lighting, equipotential bonding, partly in functional maintenance, functional maintenance, largest cross-section: 150 sqmm;
- approx. 1 615 m cable trays and cable ladders up to HxW: 60 x 600 mm with molded parts, partly in functional integrity;
- approx. 180 m fire protection ducts I30 and E30 / I90 with molded parts;
- other laying systems: installation pipes, ducts, parapet ducts;
- approx. 125 fire bulkheads;
- 21 sub-distributors with switching and fuse devices;
- Electrical installation devices with KNX control;
- 3 touch panels with KNX visualization server;
- approx. 1,500 lights, safety lights, busbars and light channels;
- approx. 295 m lightning protection system;
- equipotential bonding network;
- Building site electrical system and lighting with 7 building site distribution boards.