The measure advertised below is the installation of a fire alarm system (BMA) in a conversion of an existing building (hereinafter referred to as an existing building) of a primary school. The system is also to be used in a free-standing new building for house alarm purposes. The building stock has been gutted as far as possible and the technical systems will be 100% reinstalled.
The system is installed in accordance with DIN VDE 0833, VDE 0833-2, and DIN VDE 14675 as well as the technical connection requirements of the Krefeld fire brigade.
The building dimensions are
Duration:
- length of the building: approx. 50 m,
- Width of the building: approx. 54 m.
new building:
- length of the building: approx. 35 m,
- Width of the building: approx. 32 m.
Type and scope of the construction work:
- 1 fire alarm control panel,
- 1 pc of fire service activation (FIBS, FSD, FSE, FAT),
- 200 pcs. Autom. Detector,
- 21 pcs manual call points,
- 142 sirens (bus-controlled),
- 1 pc RAS system,
- 400 m installation of fire alarm lines / E30,
- 2 400 m installation of fire alarm lines,
- 160 m fiber optic cable.
Number of floors
Duration:
- 4 floors consisting of:
- 1 basement, ground floor, 1 upper floor, 2 upper floor
new building:
- 2 floors consisting of:
- 1 basement, ground floor.