Ventilation:
Two central ventilation units, each with 13,000 m3/h, supply all offices and ancillary rooms with supply and exhaust air.
The ducts are led through a shaft to the floors and there in the hallway or through the offices as
Flat channel distributed.
Smaller dimensions are carried out in spiral seam pipe.
There are volume flow controllers and silencers in front of the grilles in the offices. The main routes are preserved
Throttle valves, numerous fire dampers must be provided.
Only the exhaust and outside air ducts on the 3rd floor are insulated.
Quantities:
2 ventilation units with 13,000 m3/h
2100 m2 sheet metal duct system
1,460 m spiral seam pipe up to DN 250
364 pcs grille outlets in the offices
204 St Tellerventile
30 swirl outlets in the meeting rooms
369 pcs Volumetric flow regulator and limiter
523 St Silencer
165 St Brandschutzklappen
Cold:
The server room will be equipped with a split system with 5 kW.
The meeting rooms will be equipped with a 20 kW chiller on the roof and ceiling cassettes in the
Evacuate. The piping is carried out with insulated copper pipes.
Quantities:
1 pcs climate split outdoor with indoor unit, 5 kW
2 pcs outdoor units heat pumps for cooling, a total of 20 kW
5 pcs ceiling cassettes 4-sided
90m copper pipe OD 18-28mm, insulated
Ventilation:
Two central ventilation units, each with 13,000 m3/h, supply all offices and ancillary rooms with supply and exhaust air.
The ducts are led through a shaft to the floors and there in the hallway or through the offices as
Flat channel distributed.
Smaller dimensions are carried out in spiral seam pipe.
There are volume flow controllers and silencers in front of the grilles in the offices. The main routes are preserved
Throttle valves, numerous fire dampers must be provided.
Only the exhaust and outside air ducts on the 3rd floor are insulated.
Quantities:
2 ventilation units with 13,000 m3/h
2100 m2 sheet metal duct system
1,460 m spiral seam pipe up to DN 250
364 pcs grille outlets in the offices
204 St Tellerventile
30 swirl outlets in the meeting rooms
369 pcs Volumetric flow regulator and limiter
523 St Silencer
165 St Brandschutzklappen
Cold:
The server room will be equipped with a split system with 5 kW.
The meeting rooms will be equipped with a 20 kW chiller on the roof and ceiling cassettes in the
Evacuate. The piping is carried out with insulated copper pipes.
Quantities:
1 pcs climate split outdoor with indoor unit, 5 kW
2 pcs outdoor units heat pumps for cooling, a total of 20 kW
5 pcs ceiling cassettes 4-sided
90m copper pipe OD 18-28mm, insulated