The NRW.URBAN GmbH & Co. KG intends to construct a building including technical equipment and associated outdoor facilities for the accommodation of the research production battery cell at the location in Münster.
Building data:
Gross floor area: approx. 33,547 m2
Building volume: approx. 355,609 m3
Footprint of the ground floor (E0): approx. 20,367 m2
External dimensions of the building [m]: approx. 167.64 x 173.33 x 149.95 x 98.35
Main quantities for the tender (1-3):
1. KGR 441 - High and medium voltage systems:
20 pieces of transformers 1,250 kVA
approx. 170m2 system floor with grating for transformer installation
5 pieces of 10kV medium voltage switchgear
36 pieces of 10kV medium voltage switchgear fields
50 pieces of 10kV medium voltage protection devices
approx. 125m2 double floor system for the installation of 10kV medium voltage switchgear
approx. 1,300m medium voltage cables N2XS(FL)2Y indoor installation
approx. 210 pieces of 10kV end caps
approx. 32 pieces of cable testing 10kV
2. KGR 442 - Own power supply systems:
1 piece UPS system 150 kVA
1 piece UPS system 120 kVA
1 piece UPS system 60 kVA
1 piece UPS system 30 kVA
5 pieces UPS system 10 kVA
1 piece emergency power supply system 1,400 kVA in container design
1 piece underground storage tank 20m3
1 piece mobile load bank 800 kW
1 piece emergency power supply system 165 kVA in station design
4 pieces emergency light devices as central battery systems
1 piece emergency light device as a decentralized low-power system
3. KGR 443 - Low-voltage switchgear:
4 pieces of low-voltage main distributions AV, 100 kA, 5,000 A
2 pieces of low-voltage main distributions EN, 40 kA, 400 A
4 pieces of low-voltage main sub-distributions UPS, 40 kA, up to 400 A
1 piece of low-voltage main sub-distributions UPS, 65 kA, 800 A
approx. 260m2 double floor system for low voltage switchgear installation
approx. 200m busbar system 3,200 A
approx. 2,500m busbar system 2,500 A
approx. 100m busbar system 400 A
LOT-0001
Münster, Research Production Battery Cell 2nd BA Fab; Electrical TGA.
Main quantities for the tender (4-18):
4. KGR 444 - Low-voltage installation systems:
approx. 500m riser installation NYCWY 4x240/120mm2
approx. 2,000m riser installation NYCWY 4x185/95mm2
approx. 1,000m riser installation NYCWY 4x150/70mm2
approx. 1,200m riser installation NYCWY 4x120/70mm2
approx. 500m riser installation NYCWY 4x95/50mm2
approx. 1,000m riser installation NYCWY 4x70/35mm2
approx. 50 pieces of electrical connections 4x240/120mm2
approx. 100 pieces of electrical connections 4x185/95mm2
approx. 130 pieces of electrical connections 4x150/70mm2
approx. 100 pieces of electrical connections 4x120/70mm2
approx. 4,000m cable trough heavy execution as ceiling suspension
approx. 1,500m cable trough medium execution as raw floor installation
approx. 2,000m cable trough wide span execution as ceiling suspension
approx. 100,000m low-voltage installation wires
approx. 50 pieces of electrical sub-distributions in various sizes
5. KGR 445 - Lighting systems:
approx. 2,000m light channel system
2 pieces of light channel system as special design with special construction from steel
approx. 3,000m light band system
approx. 500 pieces of damp room batten lights
approx. 50 pieces of recessed downlights
approx. 50 pieces of surface-mounted downlights
approx. 115 pieces of stable lights in vertical constellation for atrium lighting
approx. 130 pieces of special floodlights for planted walls
approx. 3,500 DALI participants
approx. 250 pieces of device holders with safety light for installation on light band systems
approx. 65 pieces of device holders with emergency sign light for installation on light band systems
approx. 350 pieces of emergency lights for ceiling or pendant mounting
approx. 30 pieces of emergency lights for outdoor
approx. 300 pieces of emergency sign lights for ceiling, wall or pendant mounting
6. KGR 446 - Lightning protection and grounding systems:
approx. 2,700m round wire 8 mm / 50 mm2 AIMgSi
approx. 2,300m roof cable holders for flat roofs
approx. 800 pieces of seam clamps with clamp block
approx. 300 pieces of isolation clamps (200 kA) NIRO
approx. 30 pieces of underground separation boxes
7. KGR 449 - High-voltage installations, others:
approx. 45 pieces of sealing inserts to seal building entries
approx. 20 pieces of building entries roof
approx. 500 pieces of fire stop assemblies
8. KGR 452.2 - BOS radio:
4 pieces BOS radio central units
approx. 2,400m radiating coaxial cable 7/8"
approx. 200m coaxial cable 1/2"
approx. 400m telecommunication lines JE-H (ST)H 12x2x0.8mm
approx. 600m fiber optic outdoor cables 2x2 fibers OM3 multimode
9. KGR 452.3 - WC call system:
5 pieces of call set for accessible WC complete set 1-fold
10. KGR 453 - Time service systems:
4 pieces of touch terminal for time recording
11. KGR 456.1 - Fire alarm system (BMA):
4 pieces fire alarm central units
approx. 50 pieces bus cards
approx. 60 pieces optical smoke detectors with separator
approx. 100 multi-sensor detectors
approx. 300 multi-sensor detectors with integrated audible alarm
approx. 500 detector bases
approx. 45 pieces manual call points
approx. 70 pieces combination signal devices EN54-3/-23
approx. 120 pieces of BMA couplers
approx. 30 pieces aspiration smoke detectors
approx. 400m RAS pipe (ABS), diameter 25mm
approx. 8 pieces linear detectors
approx. 13,000m telecommunication installation cables BMA
12. KGR 456.2 - Intruder alarm system (EMA):
15 pieces LCD control panels
50 pieces HF key transponders
approx. 20 pieces infrared microwave motion detectors
approx. 50 pieces input modules
13. KGR 456.3 - Indoor video surveillance:
18 pieces indoor complete cameras 4K
14. KGR 456.4 - Access control systems (ZuKo):
approx. 12 pieces access control managers for 19" rack installation
approx. 70 pieces RFID access control readers
approx. 250 pieces RFID card/RFID tag
15. KGR 457 - Data transmission networks:
approx. 30 pieces network cabinets 42 HE
approx. 85 pieces 19" 24-fold patch panel 1HE gray, Cat.6A
approx. 9 pieces 19" 25-fold patch panel 1HE gray, Cat.3
approx. 57 pieces 19" fiber optic splice box 1HE, 48 fibers
approx. 40 pieces fiber optic splice box, 12/24/48 fibers, wall mount
approx. 3,500m fiber optic universal cable 4x 9/125
approx. 1,600m fiber optic universal cable 6x 9/125
approx. 2,200m fiber optic universal cable 12x 9/125
approx. 2,000m fiber optic universal cable 24x 9/125
approx. 4,800m fiber optic universal cable 4x12x 9/125
approx. 10,000m data cable 4x2xAWG23 simplex
approx. 55,000m data cable 2x4x2xAWG23 duplex
approx. 10,000 outdoor data cable 2x4x2xAWG23
approx. 2,200 pieces measurement permanent link class EA according to EN50173-1:2011
approx. 2,300m OTDR measurement according to DIN ISO/IEC 1463 with lead and trailing fibers from both sides
approx. 2,300m OTDR measurement according to DIN ISO/IEC 1463 with lead and trailing fibers from both sides
16. KGR 460 - Conveying systems:
2 pieces loading and passenger elevators 3,000 kg/40 persons
2 pieces passenger elevators 2,000 kg/26 persons
17. KGR 480 - Building automation:
approx. 200 pieces immersion sensors
approx. 100 pieces differential pressure sensors
approx. 134 pieces KNX presence detectors
approx. 20 pieces frost monitors
approx. 80 pieces dew point monitors
approx. 45 pieces duct smoke detectors
approx. 120 pieces repair switches
approx. 11 pieces gas warning systems
approx. 29 pieces automation devices
approx. 7,000 pieces data points design and commissioning ASE / MBE
approx. 4 pieces automation devices for fire protection dampers
approx. 112 pieces field bus modules for fire protection dampers
approx. 37 pieces automation focuses
approx. 12 pieces mounting plates for installation in RLT devices
approx. 40,000 meters power cables
approx. 56,000 meters control cables
18. KGR 540 - Technical systems in outdoor facilities:
approx. 2,300m medium voltage cables NA2XS(F)2Y 3 x (1 x 500/35 6/10KV SW) mm2 in the cable trench
approx. 5,000 pieces of cable protection plates
approx. 3,300m NYCWY 4x185/95mm2 high voltage cables to be installed in cable trenches
approx. 770m NYCWY 4x150/70mm2 high voltage cables to be installed in cable trenches
approx. 600m NYCWY 4x95/50mm2 high voltage cables to be installed in cable trenches
approx. 40 pieces of electrical connections 4x185/95mm2
approx. 10 pieces of electrical connections 4x150/70mm2
approx. 1,200m NYCWY 16x2.5mm2 control cables to be installed in cable trenches
approx. 1,000m V4A round conductor 10mm for laying in cable trenches
approx. 2,600m fiber optic outdoor cable 1x12 E9/um to be installed in conduits in cable trenches
approx. 23 pieces of cameras for outdoor skin monitoring including planning, commissioning, and implementation in a higher-level monitoring system
4 pieces of communication points stainless steel